Quick Reference Guide
48 Installation Guidelines For 60 Hz EcoGen™ Generators
OVERVOLTAGE RED
Unit will not start in
AUTO with utility loss.
Check LED’s / Screen
for alarms.
Contact an IASD.
AUXILIARY
SHUTDOWN
RED Unit will not start.
Check auxiliary
shutdown switch(es).
Set auxiliary shutdown switch(es) to
CLOSED (I).
LOW BATTERY YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
option from MAIN MENU. If battery
condition displays GOOD, contact an IASD.
If control panel displays CHECK BATTERY,
replace battery.
BATTERY
PROBLEM
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Contact an IASD.
CHARGER
WARNING
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Contact an IASD.
CHARGER
MISSING AC
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Contact an IASD.
SERVICE A YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Perform SERVICE A maintenance. Press
ENTER to clear.
SERVICE B YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Perform SERVICE B maintenance. Press
ENTER to clear.
INSPECT BATTERY YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Inspect battery. Press ENTER to clear.
Active Alarm LED Problem Action Solution