EasyManuals Logo
Home>Generac Power Systems>Portable Generator>GP Series

Generac Power Systems GP Series Diagnostic And Repair Manual

Generac Power Systems GP Series
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
Section 4 AC Diagnostic Tests
58 Diagnostic Repair Manual
Test 42 – Check Oil Pressure Switch
and Wire 86
If the engine cranks and starts, then shuts down
almost immediately, the cause may be one or more
of the following:
Low engine oil level
Low oil pressure
A defective oil pressure switch
Figure 4-52. Low Oil Pressure Switch
Procedure
1. Check engine crankcase oil level. If necessary, add
the recommended oil to the dipstick FULL mark.
NOTE: Do not overfill above the full mark.
2. Disconnect wire 86 and wire 0 from the oil pressure
switch terminals.
3. Remove the switch and install an oil pressure
gauge in its place.
4. Start the engine while observing the oil pressure
reading on gauge. Normal oil pressure is
approximately 35-40 psi with engine running.
a. If normal oil pressure is indicated, go to step
11 of this test.
b. If oil pressure is below about 10 psi, shut
engine down immediately. A problem exists in
the engine lubrication system.
NOTE: The oil pressure switch is rated at 10 psi for v-
twin engines.
NOTE: Refer to Service Manual, Generac P/N 0F6923
for engine service recommendations.
5. Remove the oil pressure gauge and install the oil
pressure switch.
NOTE: Do not connect wire 86 or wire 0 to the switch
terminals.
6. Set DMM to measure resistance.
7. Connect the meter test leads across the switch
terminals.
a. With engine shut down, Continuity should be
measured.
8. Crank and start the engine.
a. Infinity should be measured.
9. Connect one test lead to wire 0 (disconnected from
LOP).
10. Connect the other test lead to a clean frame
ground.
a. Continuity should be measured.
b. If continuity is not measured repair or replace
wire 0 between the LOP and the ground
terminal connection on the engine mount.
11. If the LOP switch tests good in steps 5-10 and oil
pressure is good in steps 2-4, but the unit still shuts
down with a LOP fault, check wire 86 for a short to
ground.
12. Set DMM to measure resistance.
13. Disconnect the J2 connector from the circuit board.
14. Remove wire 86 from the LOP switch.
15. Connect one test lead to wire 86.
16. Connect the other test lead to a clean frame
ground.
a. Infinity should be measured.
b. If Continuity is measured, repair or replace
wire 86 between the LOP switch and the J2
connector.
Results
1. If switch tests good, refer to Flow Chart.
2. Replace switch if it fails the test.
Test 43 - Check Start Stop Relay (SSR)
Procedure
1. Set DMM to measure resistance.
2. See Figure 4-53. Disconnect wire 15 and wire 229
from the Start Stop Relay (SSR).
Figure 4-53. Testing Start Stop Relay (SSR)
3. Connect one meter test lead to the terminal that
wire 15 was removed from.
4. Connect the other meter test lead to the terminal
that wire 229 was removed from.
004663
SSR
15B
1413
9 10 12
5
1 2
6
4
8
229
0
18
14
15
15
15
004630

Table of Contents

Other manuals for Generac Power Systems GP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems GP Series and is the answer not in the manual?

Generac Power Systems GP Series Specifications

General IconGeneral
BrandGenerac Power Systems
ModelGP Series
CategoryPortable Generator
LanguageEnglish

Related product manuals