301...316. EOL for Z1...Z16 (PRiMA 12,16)
Z1...Z16 line configuration, depending on detec-
tors wiring. See: “Device connecting” chapter.
0 Disabled
1 NC
2 NO
3 EOL (1.1k, or 2.2k)
4 2EOL/NC (2×1.1k)
5 2EOL/NO (2×1.1k)
Default: Z1-Z8: NC, Z9-Z16: Disabled
Zone function
321...326. Z1...Z6 zone functions (PRiMA6)
321...336. Z1...Z16 zone functions (PRiMA12,16)
Zones Z1...Z16 function selection, according to
the following list:
0 Disabled
Signals from disabled zones are ignored
by the panel.
1 Delayed (entry/exit)
Zone violation in armed state starts
count-down of the partition entry delay
(see function 211), after which an alarm
will be notified if the system will not be
disarmed during entry delay.
Violations during exit delay are ignored.
Typical use case: entry door contact.
2 Follower delayed
Zone violation during entry delay are ig-
nored. Zone violation during armed state