44 -
OPERATION INSTRUCTIONS
Daily preparations
•
Learn the functions of the control buttons and signal lamps by stud-
ying the Instruments and Control unit chapters. Find out how the
user-programmable parameters are set on this unit.
•
Open valves for water, air and, where applicable, steam.
•
Switch on the mains switch of the unit.
•
Check that recording instruments and printers have sufficient paper.
The paper of recording instrument shows a red line when it is nearly
finished.
•
Run the first steam sterilization process of the day with the chamber
empty. This heats up and drains the system pipework.
Running a process
•
Select the desired program. The selected program is indicated on the
control panel.
Parameter password
•
Before a selectable parameter can be changed, a parameter password
must be entered, after which all parameters (see Program combina-
tion) can be changed.
Password-protected programs
•
Programs that are not intended to be used routinely are protected
with a password. Some degree of consideration is called for before a
password-protected programs is chosen. Examples include test pro-
grams, programs for emergency situations, programs with selectable
parameters or programs using some sterilization medium other than
steam.
•
Load the sterilizer.
Start via operator panel Avanti
•
Make sure that cycle media are availa-
ble.
•
Close the door by pressing
Close
.
•
If the “Door locked” indicator is lit and
the
Start
button can be selected, the
machine is ready to start.