25
P 9.5 - Reset to factory settings / use of GfA-Stick
Activate the GfA-Stick with option .0 The GfA-Stick (part no. 20003696) allows readout of faults, operations,
and programming by using the GfA App. With option . 1, you delete all set menu items and reset the door
control to factory setting.
Reset to factory settings / use of GfA-Stick
Activate GfA-Stick.
.1
Reset to factory settings.
Press the OPEN Button once to select menu item . 1.
Confirm your selection by pressing the STOP Button for 3 seconds.
10
Fault correction
i
You can find detailed information on faults and how to rectify them in our
fault guide for door controls.
Download the fault guide from the GfA-Portal.
Start the fault guide using the GfA+ app.
Fault indications
Door control is off / display is dark
Possible causes Fault correction
Display is
dark /
door
control is
without
function
Measure the input voltage.
Overload
Check whether too many electrical loads are connected to the
control circuit (24 V).
Short circuit
Check whether a faulty device is connected to the control
circuit (24 V).
Water damage Check if water has entered the control box.
A different defect
Disconnect all lines (delivery status).
Replace the door control if the display stays dark.
Fault in the safety circuit
Cause of the fault Fault correction
Display alternates between F and number