WARNING:
In case of a short circuit or interruption of the analogue detection loop, only a maximum
of 32 detectors or call points (per loop) can be prevented, at any given time,
of transmitting a fire alarm. In order to assure compliance with EN54-2 clause 12.5.2 loop isolators
have to be installed every 32 devices in the loop.