AppendixA-ModbusVariableMap
Alarm Alarm
Alarm
Biteld Biteld
Biteld
Table Table
Table
ClearanindividualalarmbywritingthevaluetotheModbusregister402012(seeRunRegisters,page82).
Code Code
Code
Summary Summary
Summary
Hex Hex
Hex
AnyAllalarmsarecleared0x0000
F3HighFlow0x0001
F2LowFlow0x0002
MF
MaintenanceCounter
0x0004
P3HighPressure0x0008
P2LowPressure0x0010
F6RunawayFlow0x0020
P6RunawayPressure0x0040
SN
MinimumFillVolume0x0080
SP
MinimumFlushVolume0x0100
EU
SystemIdle
0x0200
Code Code
Code
Summary Summary
Summary
Hex Hex
Hex
QT
DoseTime0x0400
B4JobDispenseHigh0x0800
B1JobDispenseLow0x1000
G2GunOffSetpoint
0x2000
Allalarmsmaybeclearedbywriting0x0tothe
register.Ifalarmsaretobeclearedindividually,write
thebitmaskofthealarmstobecleared.IfthePLC
writecycledoesnotallowwritingthesamevalueto
theregister,oneofthepresentlyunusedbits,such
as0x80000000or0x40000000,maybeaddedtothe
bitmasktoallowthewritecycle.
Run Run
Run
Setpoint Setpoint
Setpoint
Registers Registers
Registers
Allregistersare32-bit.
Address Address
Address
Description Description
Description
Permissions Permissions
Permissions
Units Units
Units
Low Low
Low
High High
High
Notes Notes
Notes
402050Fluidsetpointas
percentageof4to
20mArange
Read/WritePercent099.9
Scaledas1%=65536
Activewhen403094=0
(See
SetupRegisters,page84)
402052Fluidsetpointasdrive
current
Read/WriteuA0320001mA=1000
Activewhen403094=3
(See
SetupRegisters,page84)
402054Fluidsetpointas
pressure
Read/Writebar032-bit
Scaledas1bar=65536
Activewhen403094=1
(See
SetupRegisters,page84)
402056
Fluidsetpointasow
rate
Read/Writecc/min065535Activwhen403094=2
(See
SetupRegisters,page84)
402058ReadbackcurrentReaduA0320001mA=1000
402060Atomizingairsetpointas
percentageof4to20
mArange
Read/WritePercent099.9
Scaledas1%=65536
Activewhen403094=0
(See
SetupRegisters,page84)
402062Unused
402064Unused
402066Unused
402068Unused
3A6948A83