DC INVERTER MULTI VRF INSTALLATION
123
4. The installation place should be horizontal.
5. Select the place, where coagulated water is easy to discharge and outside unit to be
connected.
6. Above 18000mm between the earth and indoor unit should be ensured for maintenance and
repair.
7. Use hoisting screw to check if the installation place can withstand 4 times weight of the units and
strengthen it before installing.
4.5.2
Dimensions Data
Important notice:
Drilling the hole of the ceiling and installing the units must be operated by
professionals
4.5.3 Clearance data