DC INVERTER MULTI VRF INSTALLATION
125
Drainage pipe
1. Installing drainage pipe
The diameter of drainage pipe should be larger than that of connecting pipe. (Polythene pipe:
dimension: outer diameter 25mm wall thickness1.5mm)
Drainage pipe should be as short as possible and drooping gradient at least 1/100 to avoid
the formation of air bubble.
If drainage hose cannot have enough drooping gradient, drainage raising pipe should be
installed.
In order not to bend the drainage hose, the distance between hoisting stands should be 1 to
1.5m..
With accessory drainage hose and clamp, insert the drainage hose into the drainage faucet,
and then tighten the clamp.
Entwine the clamp of drainage hose with the big sponge to isolate heat.
Isolate heat for the outdoor drainage host.
Sponge (Gray)
Drainage Hose
Notice for drainage raising pipe
The installation height should be less than 280mm.
A right angle should be formed by the drainage raising pipe and unit, which should not be
more than 300mm far from the unit.