DC INVERTER MULTI VRF INSTALLATION
135
2. Install the panel
Screw the 4 hexagon head screws under the latches in about 15mm. (The panel would rise)
Adjust the panel by turning it toward the direction pointed by the arrow as shown in fig.4, so that
the adjust board connect the ceiling well.
Tighten the screws until the thickness of the sealing material between panel and indoor unit
reduced to 5-8mm.
Air outlet vent
Ceiling
Decoration panel
5mm to 8mm
.
Indoor unit
Swing flap motor
Sealing material
Piping position
Bolt attachment
Bolt attachment
Fig 4
Note
1. Improper screwing of the screws may cause the troubles shown in fig.5.