EasyManuals Logo

Gree FLEXX Series Service Manual

Gree FLEXX Series
121 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
GREE DC INVERTER HEAT PUMP CONDENSING UNIT
29
Troubleshooting
E3 protection
Check if the
system low
pressure is lower
than 0.05MPa
No
Yes
Charge
refrigerant
according to the
requirement and
then turn on the unit
to see if E3
protection still
occurs
Yes
Enter
debugging mode
through wired
controller and select
without refrigerant
lacking protection; then
turn on the unit to see
if E3 protection still
occurs
No
Completely open the liquid
valve and gas valve of outdoor
unit
Check if the liquid
valve and gas
valve of outdoor
unit open
completely
Yes
Yes
Yes
Weld the leakage point and
recharge refrigerant after
vacuum pumping and pressure
retaining are passed
Check if there is
leakage in the
pipeline
Reconnect wire according to
the circuit diagram or replace
the pressure switch
Yes
35-85 outdoor units
are without low pressure switch and
check if the wiring of mainboard is
normal;100-160 outdoor units are
with low pressure switch and
check if the low pressure
switch and its wiring
are normal
Replace the outdoor main
control board
No
3.4.3 “E4” Compressor Air Discharge High-temperature Protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
Test the compressor discharge temperature through compressor discharge pipe and shell top temperature
sensor. If the tested temperature value is higher than 115, the unit will stop for protection

Other manuals for Gree FLEXX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree FLEXX Series and is the answer not in the manual?

Gree FLEXX Series Specifications

General IconGeneral
TypeHeat Pump
SeriesFLEXX
SEERUp to 20
HSPFUp to 10
RefrigerantR410A
Heating Operation Range-22°F to 75°F
Cooling Operation Range5°F to 122°F
Operating Temperature Range (Heating)-22°F to 75°F
Operating Temperature Range (Cooling)5°F to 122°F
Energy Efficiency Ratio (EER)Up to 12.5
Dimensions (Outdoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
Compressor TypeInverter
Power Supply208/230V, 1Ph, 60Hz
Noise LevelAs low as 55 dB(A)

Related product manuals