GREE DC INVERTER HEAT PUMP CONDENSING UNIT
82
Model: FLEXX36HP230V1AO
Removal of electronic expansion valve
NOTE:Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step
Picture
Work instruction
1. Remove the
electric box.
Remove the upper, lower
and front panels.
Loosen the wire clamp at
the bottom of the electric
box
Unscrew the screws of
electric box.
The connection wires
inside and outside the
electric box should be
removed.
When removing the
electric box, be careful to
protect the components.
2. Remove the
fixed block.
Remove the fixed block
between the electronic
expansion valve and the
pipe.

Other manuals for Gree FLEXX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree FLEXX Series and is the answer not in the manual?

Gree FLEXX Series Specifications

General IconGeneral
TypeHeat Pump
SeriesFLEXX
SEERUp to 20
HSPFUp to 10
RefrigerantR410A
Heating Operation Range-22°F to 75°F
Cooling Operation Range5°F to 122°F
Operating Temperature Range (Heating)-22°F to 75°F
Operating Temperature Range (Cooling)5°F to 122°F
Energy Efficiency Ratio (EER)Up to 12.5
Dimensions (Outdoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
Compressor TypeInverter
Power Supply208/230V, 1Ph, 60Hz
Noise LevelAs low as 55 dB(A)

Related product manuals