Unit Control
52
30
Air removal
Air removal
On/Off
Off
/
31
Address
Address
[1~125]
[127~253]
1
/
32
Gate-Controll
er
Gate-Ctrl.
On/Off
Off
/
3.2.2.1 Mode
It enables the user to select the run mode of the unit. When the water tank is not prepared, then only
Cool
and
Heat
modes are available. When the water tank has been prepared and
Water Tank
is set to
With” through the wired controller (see Section 3.2.2.26 for more details), then
Cool
,
Heat
,
Hot water
,
Heat + hot water
, and
Cool + hot water
modes are available. In this case,
Heat + hot water
or C
ool +
hot water
can be given priority. (see Section 3.2.2.5 and3. 2.2.6 for more details), which is the default
setting before delivery.
[Operation Instructions]
At the equipment OFF state, access to the
FUNCTION
page and then move through the Left/Right
key the cursor to the
Mode
whose characters will be reversed, then press the Up/Down
key to modify its setting.
[Notes]
The “Heatmode is defaulted when the unit is energized for the first time.
The running mode is allowed to be changed only when the unit is not in operation. If it is done
with the unit being on, a window will pop up, warningPlease turn off the system first”.
When the water tank is disabled, only the ‘Heat” or the “Coolmode is allowed.
When the water tank is enabled, Cool”, Heat”, Hot water”, Cool+hot waterr”, “Heat+hot
water” is allowed.
For the heat pump, the “Cool” mode is allowed; for the heating only unit, Cool+ Hot waterand
“Cool” are unallowable.
This setting can be memorized upon power failure.
3.2.2.2 Control State (Ctrl. state)
It enables the user to configure the control state to leaving water temperature or room temperature.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Ctrl. state
”, then, configure it through the Up/Down key
.
[Notes]
If Remote sensor is set to With”, T-out water and T-room are available. While if
Remote Sensor” is set to “Without”, onlyT-out water” is selectable.
This setting will be memorized upon power failure.
3. 2.2.3 Fast Hot Water
When hot water is needed urgently, this function can be configured to be “On”, In this case, the heat
pump and the water tank heater will work together to generate sanitary hot water in a quickest way.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Fast hot water
”, then, configure it through the Up/Down key
, “
On
” or “
Off
”.

Table of Contents