Unit Control
53
[Notes]
① It works only when “Water tank” is set to “With”.
② This setting will be memorized upon power failure.
3. 2.2.4 T-water Ctrl (Water Temperature Control for Heating)
There are two options for the leaving water temperature control, high-temperature water circulation
(
High temp
) and normal-temperature water circulation (
Normal temp
). When “
Floor config
” is set to
“
With
” (see 2.2.29), then the leaving water temperature control is defaulted to be “
Normal temp
”. When
“
FCU config
”(see 2.2.31) or “
Radia config
”(see 2.2.30) is set to“
With
”, the leaving water temperature
can be configured to either “
High temp
” or “
Normal temp
”.
[Notes]
“Floor config”, “FCU config”, and “Radia config” all can be configured to be “With”. However, as
long as “Floor config” is configure to be “With”, only “Normal temp” is available.
[Operation Instructions]
Go to the
FUNCTION
page and locate “
T-water ctrl.
”, then, configure it through the Up/Down
key , “
High temp.
” or “
Low temp.
”.
[Notes]
① When this setting is changed, the following parameters will return to the default values.
② This setting will be memorized upon power failure.
3.2.2.5 Cool + Hot water
This compound mode enables the user to give priority to the “
Cool
” or “
Hot water
” mode depending
on the actual demand.
[Operation Instructions]
Go to the
FUNCTION
page and locate “
Cool+hot water
”, then, configure it through the Up/Down
key , “
Cool
” or “
Hot water
”.
[Notes]
① “Hot water” will take precedence only when “Water tank” is available, other it will tell
“Reserved”.
② This setting will be memorized upon power failure.
3.2.2.6 Heat + Hot water
This compound mode enables the user to give priority to the “
Heat
” or “
Hot water
” mode depending
on the actual demand.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Heat+hot water
, then, configure it through the Up/Down key
, “
Heat
” or “
Hot water
”.