Note:
A RCD 30mA type A is required as minimum.
6.11 Electrical requirements
6.11.1 Upstream requirements
Charging station
Electrical connection must be carried out by a professional electrician according to the
local regulations.
Charging station must be connected to an electrical network with the following
characteristics:
• 3 Phases (3P + PE +N*) (*Neutral required in case of AC socket).
• 380 Vac +/- 10%
• 50/60 Hz
The main switch disconnector, located upstream of the charger power supply, must be
rated by the installer.
Refer to local regulations, maximum current and voltage drop to select the upstream
protection.
6.11.2 Grounding Instructions
Observe the following rules for the grounding instructions:
• Ground impedance must be lower than 20 ohms in dry conditions where the charging
station is installed.