CALIBRATION
-forOpenChannelFlow
1.Beforestartingthecalibrationdetermine:
a) MAXRANGE =____________________
(Maximumrange=distancefromtheSensorto
Zerolevelpoint)
b) MAXLEVEL =____________________
(Maximumlevelofflowthroughflumeorweir)
c) MINRANGE =__________________
(DistancefromsensortoMaxLevel)
Minimumrange=MAXRANGE-MAXLEVEL
(mustbeatleast8"/20.3cmdependingonsensor
model).
2.Checkthemaximumrangewiththesensorinstalledby:
a) Use Æ togetto UNITS/MODEthen È togetto
Range,then S
tore? Yes
(NOTE:flowmustbeatzeroflow)
or
b) Carefullymeasuredistancefromsensortozero
levelwithtapemeasure.
NOTE:TheSLT32willnotdetecttargetsbeyonduser
entered MaxRg.
SLT32Level&FlowMonitor
ManualSeriesB.11
Page 12
MinRg 1.333 ft
MaxRg 32.00 ft
4mA @ 0.00 %
20mA @ 100.00 %
CALIBRATION
Damping 20 %
RejTime 08 s
Store? Yes
RELAY PARAMETERS
FLUME SELECTION
PALMERBOWLUS
SENSOR
ZERO LEVEL
MAX
RANGE
MIN
RANGE
MAX LEVEL
V-NOTCH
SENSOR
ZERO LEVEL
MAX
RANGE
MAX LEVEL
MIN
RANGE