ERROR/WARNINGMESSAGES
"ECHOLOSS"(flashing) Novalidechoesreceivedwithinthe LOETIME setting.SeeFIELD
TROUBLESHOOTING(F).In Level modetheSLT32willholdthe
displayandoutputsatthelastreadinguntilanewechoisreceived.In
FLOW modeitwilldisplay 0.00 andtotalizationwillstopuntilanechois
received.RefertoECHOSTRENGTHinstructions.
Er:ILLEGALMinRg Thevalueenteredfor MinRg (MinimumRange)islessthan8"(20.3cm).
MinRg mustbegreaterthanorequalto8"(20.3cm)forPZ12sensors.
MinimumRangeforPZ32Tsensorsmustbegreaterthanorequalto
12"/30.5cmandforoptionalPZ52Tsensormustbegreaterthanorequal
to16"(40.6cm).
Er:ILLEGALUNITS YourchoiceofUNITSexceedsamaximumvalueof9,999,999.UseUS
MGD,ImpMGDorm3/dsothatUNITSwillbe9,999,999orless.
Err:ILLEGALSPAN 1.Thevalueenteredfor MaxRg isthesameorlessthan MinRg +2".
Maximumrange must
begreaterthanminimumrangeandlessthan102ft.
(31.09m).(Note:toinvertthescaleandoutputs,choose Level insteadof
Range selectioninthe UNITS/MODE menu.)
2.ForRectangularWeirswithEndContractions,theSPAN(MaxRg -
MinRg)mustbelessthan½theweirsize(eg:12"crestwidth,SPAN
mustbe6"orless).
-or- YourchoiceofUnitsexceeds9,999,999.UseUSMG/d,IMG/dorm3/dso
thatUnitswillbe9,999,999orless
ERR:ILLEGAL
SETPOINTS
ONorOFFsetpointis< MinRg or> MaxRg
NORMAL/REVERSED
SETPOINTSMIXED!
RelayshavebeenselectedforPumpAlternationandhavebeencalibrated
inoppositemodes.Anyalternatingrelaysmustbecalibratedinthesame
mode:
1.withONsetpoint>OFFsetpoint,or
2.withOFFsetpoint>ONsetpoint
TEMP*23.5C *IndicatesTemperatureCompensationfault.Checksensorconnections.
ECHOTOOCLOSE Indicatesthatthetargetislessthan MinRg distancefromthesensor(too
closetothesensor).
!!SENSOROPEN! Instrumenthasdetectedsensorconnection/cableOpen.
!SENSORSHORTED! Instrumenthasdetectedsensorconnection/cableShorted.