Flow
AppearsinFlowmodeonly.Press È to RFunction and Æ toselect Pump, LoAlm (low
alarm)or HiAlm (highalarm).
Pump mode
-press È and Æ andsetrelayOnandOffsetpoint.
LoAlm mode
-press È andsetrelayOnpoint.Relaywillbeenergizedwithlevels
belowtheOnpointandde-energizedwithlevelsabovetheOnpoint.
HiAlm mode
-press È andsetrelayOnpoint.Relaywillbeenergizedwithlevels
abovetheOnpointandde-energizedwithlevelsbelowtheOnpoint.
LOE
(LossOfEcho)
-press Æ toselect Off Æ On Æ Hold.Inalossofechocondition,the
relaywillturnOff(de-energize),On(energize)orHolditscurrent
state.Eachrelaycanbeindividuallyconfigured.Press È.
ALT permitsrelayscalibratedinPumpmodetobe
alternatedautomatically.Pumpalternationallows
evenpumpwearinpumpingstationapplications.
ALT (-None-)indicatesthatnorelayshavebeen
programmedinPumpmode.
ALT123- Press Æ toplacecursor(underline)
undertherelaynumbertobeprogrammedfor
alternationandpress Ç or È tohighlight.Repeat
untilallrelaystobealternatedarehighlighted.
Note:AlternatingpumpsmusthavedifferentOn
setpointstoalternatecorrectly,otherwise
alternatingpumpswillturnOnatthesametime.
Press È to S
tore?Yes and Æ to Yes.Press Ç or È tosaveyourRelaysettings.
SLT32Level&FlowMonitor
ManualSeriesB.11
Page 15
PUMP ALTERNATION (R1, R2, R3)
LEAD
PUMP
LAG
PUMP 1
1st CYCLE
2nd CYCLE
3rd CYCLE
...ETC
1
2
2
3
3
1
LAG
PUMP 2
3
1
2