SLT32V2.77 showssoftwareversioninstalled
ViewCodes?Yes
Select Y
es andthen È todisplayaninstrumentperformancecode.Faults
detectedbytheinstrumentarestoredinthecodeandwillberequestedby
Greylineifyoucallforserviceorassistance.
Tag EnterInstrumentTagnumber(0-9999)
DateMMDD/YYYY
(withoptionalDataLogger)Press Æ and Ç or È tochangeMonth,DayYear.
TimeHH:MM:SS
(withoptionalDataLogger)Press Æ and Ç or È tochangeHours,Minutes,
Seconds
LOETIME
Press Æ and Ç or È tochangethenumberofsecondswithoutreceivingan
echobeforetheSLT32displays ECHOLOSS,andControlrelayschangestate
ascalibratedunderRelayParameters.
Factorydefaultis30secondsandisrecommendedformostapplications,
Minimumis10secondsandmaximumis60seconds.
ResetTot?Yes (FLOW modeonly)Positionthecursorunder Y
es toresetthetotalizer.Store
thisselectionatthe Store? Yes prompt.
Temp25.0C
Indicatescurrenttemperatureatthesensorhead.Press Æ to MinTemp and Æ
to MaxTemp todisplaytheminimumandmaximumtemperaturestheSLT32
hassensed.Press Æ toDisplay°C
°F.Positionthecursorunder°C forcelcius
displayor°F forFarenheightdisplay.Press È toreturnto Temp.
ISB?:NoYes Select Y
es onlywhentheinstrumentisequippedwithanoptionalIntrinsic
SafetyBarrierforsensormountinginhazardouslocations.Thissetting
compensatesfortheelectricalcharacteristicsofanIntrinsicSafetyBarrier.
Defaults?Yes
Press Æ 3timestoselect Y
es.Storetoerase all usersettingsandreturn
instrumenttofactorydefaultsettings.
Simul TheOutputsimulationfunctioncontrolsthe4-20mAoutput,digitaldisplay
andcontrolrelays.Useittosimplifycalibrationofremotedevicessuchas
chartrecordersorremotedisplays,andtotestRelayset-points.Simulation
digitsareshownasapercentageoffullscale.Usethe Ç and È Arrowkeysto
simulate 0% (4mA), 100% (20mA),andincrementsof.05%(.008mA).
Incrementswillautomaticallyacceleratewhenthe Ç or È iscontinuously
pressed.
4mAADJ
20mAADJ
Usetofinetunethe4mAand20mAcalibrationofthe4-20mAoutput.
Adjustmentrangeis+1mAto-1mAin0.002mAsteps
Important
:The4-20mAoutputwillbeforcedto4mAand20mArespectively
duringtheseadjustments.
NewPassword positioncursorunderdigitsandsetnewnumberbetween 00 and 99.
Com244896192 Optional(withDataLogger)SpeedofRS-232Ctransmission.Select 2400,
4800, 9600 or 19200 baudrate(mustbesettomatchbaudratein'Greyline
Logger'softwareandanymodemsusedforserialcommunication).