3.4 Electrical connection
DANGER
Electric shock
Death or serious personal injury
All electrical connections must be carried out by a
qualified electrician in accordance with local regula-
tions.
DANGER
Electric shock
Death or serious personal injury
Switch off the power supply before starting any work
on the product. Make sure that the power supply can-
not be accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
Connect the pump to protective earth.
DANGER
Electric shock
Death or serious personal injury
In case of an insulation fault, the fault current may be
a pulsating DC. Observe national legislation about re-
quirements for and selection of Residual Current De-
vice (RCD) when installing the pump.
The pump is not a safety component and cannot be used
to ensure functional safety in the final appliance.
The motor requires no external motor protection.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate. See section Nameplate.
Connect the pump to the power supply with the plug supplied
with the pump. See steps 1 to 7.
Related information
5.4.1 Nameplate
3.4.1
Assembling the installer plug
Step Action Illustration
1
Loosen the cable
gland and unscrew
the union nut in the
centre of the termi-
nal cover.
TM068542TM070366
2
Detach the terminal
cover.
TM068543
3
Pull the power cable
through the cable
gland and terminal
cover.
0/Off
1/On
TM068544
4
Strip the cable con-
ductors as illustra-
ted.
42 mm
32 mm
Ø 5.5 - 10 mm
0.5 - 1.5 mm
2
8 mm
L
PE
N
TM068545
5
Loosen the screws
on the power supply
plug and connect
the cable conduc-
tors.
TM068546
x 3
TM068547
8
English (GB)