• Inverse function
The setpoint is influenced inversely from 0 to 100 %.
See fig. 58.
Fig. 58 Inverse function
•"Inverse with Stop" and "Inverse with Min."
– Inverse with Stop
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Stop".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal".
See fig. 59.
– Inverse with Min.
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal".
See fig. 59.
Fig. 59 "Inverse with Stop" and "Inverse with Min."
• Influence table
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
Fig. 60 Influence table
• Influence table with Stop at Min.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 61.
Fig. 61 Influence table with Stop at Min.
TM05 6283 4612TM05 6283 4612
Setpoint influence [%]
External input [%]
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
TM05 6284 4612TM05 6285 4612
Setpoint influence [%]
External
input [%]
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop