EasyManua.ls Logo

GSK DA98A - Page 63

GSK DA98A
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DA98A AC Servo Drive Unit
User Manual
53
changed as the load is changed. Generally, the bigger the load inertia is, the smaller
the [Speed integral time constant] setting value is.
z Position control
1 Set proper [Speed proportional gain] and [Speed integral time constant] by the
methods above.
2 Set <position feedforward gain> (parameter No.10) for 0%.
3 [Position proportional gain]parameter No.9 Its setting value should be as large as
possible in a stable range. If it is too large, the track characteristic of position
instruction is good and the lag error is small, but there may be oscillation when
positioning stops.
4 If high position track characteristic is required, the setting value of <position
feedforward gain> may be increased. If it is too big, overshooting may occur.
Note 1 If [position proportional gain] setting value is small, the system is stable, but of
position track characteristic gets bad and lag error is large. If high [position
proportional gain] is needed, increase the setting value of
[acceleration/deceleration time constant] (parameter No.40, 41) to avoid the
overshooting.
Note 2 When [position feedforward gain] setting value is to be increased, if the system
is unstable, [acceleration/deceleration time constant] setting value can be
increased to avoid the overshooting.
Note 3 [Position proportional gain] setting values are as following table:
Rigidity
[Position proportional gain]
Low rigidity
1020/s
Medium rigidity
3050/s
High rigidity
5070/s
2 Adjustment diagram of primary parameters

Related product manuals