202 
Over temperature protection (OHP) 
Incorrect sensing connection 
protection (SENSE) 
Low AC input protection (AC-FAIL) 
Power limit (POWER LIMIT) 
Approx. 105% of rated output power 
Analog Programming and Monitoring 
 
External voltage control output 
voltage 
Accuracy and linearity: ±0.5% of rated output voltage. 
External voltage control output 
current 
Accuracy and linearity: ±1% of rated output current. 
External resistor control output 
voltage 
Accuracy and linearity: ±1% of rated output voltage. 
External resistor control output 
current 
Accuracy and linearity: ±1.5% of rated output current. 
Turns the output off with a LOW (0V to 0.5V) or short-
circuit. 
Possible logic selections: 
Turn the output on using a LOW (0V to 0.5V) or short-
circuit, turn the output off using a HIGH (4.5V to 5V) or 
open-circuit. 
Turn the output on using a HIGH (4.5V to 5V) or open-
circuit, turn the output off using a LOW (0V to 0.5V) or 
short-circuit. 
Clear alarms with a LOW (0V to 0.5V) or short-circuit. 
CV/CC/ALM/PWR ON/OUT 
ON indicator 
Photo coupler open collector output; Maximum voltage 
30V, maximum sink current 8mA. 
Maximum low level output = 0.8V; minimum high level 
output = 2V; Maximum source current = 8mA.  
Maximum low level input voltage = 0.8V; minimum high 
level input votage = 2.0V, Maximum sink current = 8mA. 