6.3.3.11 Function set to SYSTEM ERROR working mode
SYSTEM ERROR
WARNING LIST
Default value: DISABLED
ENABLED: Monitors the internal warning bits of every probe.
DISABLED: Monitoring is disabled.
ERROR LIST
Default value: DISABLED
ENABLED: Monitors the internal error bits of every probe.
DISABLED: Monitoring is disabled.
SENSOR MISSING
Default value: DISABLED
Monitors the connection of every connected probe.
ENABLED: Monitoring is active.
DISABLED: Monitoring is not active.
ON DELAY
(0 s–999 s)
Default value: 5 seconds
Sets a delay for the relay to turn on.
OFF DELAY
(0 s–999 s)
Default value: 5 seconds
Sets a delay for the relay to turn off.
LOG INTERVAL
Default value: OFF
Sets the interval for logging the displayed value into the data logger.
Options: OFF, 5 min, 10 min, 15 min, 20 min, 30 min.