Note: 1. is the position of delivery 2. In this system, SW07 is fixed on side of OFF, do not change it into
the side of ON.
99
6. LED display on inverter PCB
According to the position of SW01, the 4 LED (D25~D28) of frequency conversion can express the following content:
(1) If the LED displaying <IGBT short circuit> protection has no abnormal locking, when shortening time, it will
flicker in 5 Hz frequency.
(2) When conducting protection action, the LED displaying protection function will flicker in 5 Hz frequency, other
LED will be lighted.
For example: IGBT short
circuit protection action
Current detection circuit
protection action
(3) Do not display the number of protection action of high pressure
SW01
D25
D25
D26 D27 D28
D26 D27 D28
1 2
OFF OFF
IGBT short circuit
protection action
Compressor
protection action
Overcurrent
protection action
High pressure
switch action
ON OFF
OFF ON
ONON
No
Current detection
circuit protection
action
Counter of protection action
Normal
Protection action
Serial receiving Sx (frequency data)
Serial transmitting Sy (frequency data)
: Lamp ON : Lamp OFF : Flicker in 5 Hz : Flicker in 1 Hz
7. Switching function of I/F PCB
Switch No.
Type of switch
Function
SW01
SW02
SW03
16-digit knob switch (0~15)
Displaying switching (1)
7-segment nixie tube display switching
16 digit knob switch (0~15)
Displaying switching (2)
7-segment nixie tube display switching
3-digit dial switch
1
2
3
Back up running of
inverter compressor
ON: back up running OFF: usual running
Back up running of
commercial
compressor
ON: back up running OFF: usual running
Selectable function
switching
ON: requiring control
OFF: Snowfall pr-
eventing fan control
SW04
Micro switch
“Running” for
maintenance
If pressed down, indoor unit runs
SW05
Micro switch
“stopping” for
maintenance
If pressed down, indoor unit stops
SW06
3-digit dial switch
1
Pd sensor back up
running
ON: back up running OFF: usual running
ON: back up running OFF: usual running
ON: 17~30 OFF: 1~16
2
3
Ps sensor back up
running
Not used
SW07
1-digit dial switch
Indoor indicates
switching
ON: OFF:
(see page 115,116)