4. Function of outdoor unit for commanding ON/OFF of indoor unit group
No. Function Outline Setting troubleshooting method
4-1
Cool trial run
All the indoor unit groups connected are
simultaneously set to the trial run mode.
Note: Conducting control action, same as
the command usually sent out by the
remote controller.
[setting]
Use SW01 "0", SW02 "11", press SW04 for
over 2 seconds;
[eliminating]
When changing SW01, Sw02 into other
positions, use remote controller to eliminate.
4-2
Heat trial run
All the indoor unit groups connected are
simultaneously set to the trial run mode
Note: Conducting control action, same as
the command usually sent out by the
remote controller.
[setting]
Use SW01 "0", SW02 "12", press SW04 for
over 2 seconds;
[eliminating]
When changing SW01, Sw02 into other
positions, use remote controller to eliminate.
4-3
Simultaneously
running
Make all the indoor unit groups connected
run simultaneously.
Note: Running content should be as per the
setting of remote controller.
[setting]
Use SW01"0", SW02 "14", press SW04 for
over 4 seconds;
[eliminating]
Use remote controller to eliminate.
Simultaneously
stopping
Make the entire indoor unit groups
connected stop simultaneously.
[setting]
Use SW01 "0", SW02 "14", press SW05 for
over 4 seconds;
[eliminating]
Use remote controller to eliminate.
Individually
running
Make individual unit group specified run.
Note: Running content should be as per the
setting of remote controller. Other indoor
unit groups should maintain their original
state.
[setting]
For SW01 "15", set SW02 to the address
number (0~15) of indoor unit to be run, press
SW04 for over 2 seconds
[eliminating]
Use remote controller to eliminate.
Note: This function of "Run/Stop" only indicates the function of signal of run/stop sending out from outdoor unit to
indoor unit group other than the function that the signal is sent out again due to the reason that the indoor unit
group does not submit to the signal first sent out.
Individually
stopping
Make individual unit group specified stop.
Note: Other indoor unit groups should mai-
ntain their original state.
[setting]
For SW01 "15", set SW02 to the address
number (1~16) of indoor unit to be run, press
SW05 for over 2 seconds
[eliminating]
Use remote/controller to-eliminate.