EasyManua.ls Logo

Haier AU96NFTAHA - Judging Method for Fault of Display of Remote Controller

Haier AU96NFTAHA
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55
3. Judging method for fault of display of remote controller
A.Simple remote controller
(1) Check display operationFor fault display operation, pressing "check" button can confirm inspection code. Refer to the detailed contentfor fault display in the following page.
C
®
FAN ONLY
COOL
HEAT
AUTO
CHECK
12
AUTO
FIXING
GRUP
NUMBER
UNIT
NUMBER
CENTRALIZED
MANAGEMENT
STANDBY
FILTER RESET
PREHEAT
DEFROST
LOUVER
MANUAL
MODE FAN TEMP
FILTER
RESET
CHECK
MODE
ON/OFF
LCD displays the reason of "standby" Indoor unit group with cool mode beingset due to prior to heat control When the capability of indoor unit group is overloaded Selection of indoor unit group whose runningmode is opposite to the running mode(cold/heat) and switch setting content ofoutdoor unit When the phase sequence of power wiringof outdoor unit is wrong
Check buttonPress it for 0.5 second to display inspection codePress it for 3 seconds to reset the indoor unit(when the indoor unit is in the state of stoppingdue to its abnormality)Press it for 10 seconds to clear inspectioninformation in addition to resetting the indoorunit.
Reset buttonWhen using it, press the button in the hole, thepower of remote controller will be reset (clearall information)