29
No. Item Specification
Remarks
4
Capacity automatic
control
(1) Send running frequency command to outdoor unit according to
the difference of Ta and Ts.
Compressor OFF
+1
Ts
-1
-2
SF
SD
SB
S9
S7
S5
S3
S0
SD
SB
S9
S7
S5
S3
S0
Compressor OFF
Note: The running frequency in the above diagram may change due to
protection control of outdoor unit.
Ts: setting
temperature
Ta: room
temperature
Capacity
modification
(1) Control of frequency modification
Modify the frequency of outdoor unit to make the current capacity
maintain a certain level of capacity.
(2) Modification control of PMV opening
Modify PMV opening to make the refrigerant of indoor unit under
optimum state.
5
Cool Heat
+2
T s
-1
+1