16
R649c
SEPTEMBER 2018
Evaporator tons at 1F temperature differential, valve capacities are conservative.
MCR AND MCV HOT GAS SOLENOID DEFROST CAPACITIES
EVAPORTATOR SIZE TONS
Refrigerant
Port Size (mm)
3/4˝
(20)
1˝
(25)
1-1/4˝
(32)
1-1/2˝
(40)
2˝
(50)
Ammonia
9-15
(32-53)
15-28
(53-99)
28-39
(99-137)
39-73
(137-256)
73-106
(256-373)
R-22
6-8
(21-28)
8-15
(28-53)
15-20
(53-70)
20-32
(70-113)
32-47
(113-165)
R-134a
1-4
(4-14)
4-8
(14-28)
8-12
(28-42)
12-20
(42-70)
20-38
(70-134)
R-404
3-6
(11-22)
6-10
(22-35)
10-18
(35-63)
18-30
(63-106)
30-44
(106-155)
R-507
1-4
(4-14)
4-8
(14-28)
8-12
(28-42)
12-20
(42-70)
20-38
(70-134)
TABLE 24
MOTORIZED CONTROL VALVE CAPACITIES