Programmable Temperature & Humidity Controller
48
Wait operation
Wait operation
Wait time
Wait range
Wait operation is
cancelled because PV
is within defined wait range
Wait operation is
started because
PV is out of
defined wait range
SEG. progress
without wait mode
SEG progress
with wait mode
SEG. progress
without wait mode
SEG progress
with wait mode
Wait time
setting
Wait operation
Wait range
Wait operation is
started because
PV is out of
defined wait range
Wait operation is
cancelled because
PV is within defined
wait range
Wait operation
Wait time
Wait range
Wait operation is
cancelled because PV
is within defined wait range
Wait operation is
started because
PV is out of
defined wait range
SEG. progress
without wait mode
SEG progress
with wait mode
SEG. progress
without wait mode
SEG progress
with wait mode
Wait time
setting
Wait operation
Wait range
Wait operation is
started because
PV is out of
defined wait range
Wait operation is
cancelled because
PV is within defined
wait range
If measurement (PV) is out of wait range, it waits until the measurement(PV) enters the wait range for
defined wait time.
If wait time is elapsed, it moves to next segment even though measurement(PV) is out of wait range.
Operation start mode
SV setting value
SV setting value
PV measurement
PV measurement
Start of program operation Start of program operation
[Start mode SSV] [Start mode SPV]