Programmable Temperature & Humidity Controller
32
2. Operation setting
Screen for operation screen, operation, and data save settings.
▶ Operation setting
1) Select a control method.
2) With an initial operation, a measurement may exceed the setting value, which is called Over Shoot.
Select the fuzzy function to control the over shoot. With the fuzzy function selected, there may be
Under Shoot that the ascending time is delayed according to the load or measurement doesn't
reach the setting value.
3) For constant-value control, set temperature change rate by time(minute).
(Enabled for constant-value control)
4) For constant-value control, it operates for set time and then stops.
(Enabled for constant-value control)
5) Set tag names for Ch.1 and Ch.2. Up to 10 English characters(5 Korean characters) can be entered,
and set tag is displayed on the operation screen.
Parameter Description
Constant To control temperature with certain setting value(SV).
Program
To control measurement with change of setting values over time.
It is controlled according to a pattern set in [Program] – [Pattern setting].
Parameter Setting range Default
Operation type
Constant value, Program Constant value
Fuzzy function
Cancel, Set Cancel
SV change rate for Ch.1
0.0 - 3000.0[℃/min] 0.0
Constant-value operation
time for Ch.1
0 - 9999[min] 0
SV change rate for Ch.1 0.0 - 3000.0[℃/min] 0.0
Constant-value operation
time for Ch.1
0 - 9999[min] 0
Ch.1 tag Up to 10 English characters CHANNEL #1
Ch.2 tag Up to 10 English characters CHANNEL #2
[Temperature setting parameter]
Fig. 46) Operation setting