Programmable Temperature & Humidity Controller
56
1. Control mode
- Set heating and heating/cooling controls.
2. Output cycle
- If the control output is “SSR,” set the cycle for control output operation.
3. Direction of output
- Set Normal operation or Reverse operation.
4. Prevention of over integral
- Set over integral prevention function mode.
- If it is MANUAL, the over integral prevention ratio can be manually set.
▶ Control output
2. Control/transmission output setting
Parameter Setting range Default
Control mode
Heating and Heating/Cooling control
Heating control
Output cycle 1 - 1000 1
Output type SSR and SCR SSR
Direction of output Normal operation and Reverse operation Reverse operation
Prevention of over integral 50 % - 200 % 100 %
[Control output parameter]
SSR cycle
If Voltage pulse output[SSR] is selected, the output is 20 % - 100 %. According to the voltage pulse
output cycle, control output is ON for certain time (OFF for the rest).
Fig. 85) Control output (Heating/cooling) Fig. 86) Control output (Heating)
Fig. 87) SSR output operation