Wiring
14
Remote System Connection - Customer Supplied Cable
Gladiator Gen 3 Microwave Series
Remote Sender Remote Receiver
Alternate Cable Colour Equivalents
Pairs HAWK Belden 3120A Dekoron
Pair 1 Red
Black
Red
Black
White 1
Black 1
Pair 2 White
Blue
Yellow
Green
White 2
Black 2
Pair 3 Brown
---
Brown
White (not used)
White 3
Black 3 (not used)
Pair 4 not used not used not used
Alternate Cable Type Between
AmplierandSensors
• 6 or 8 conductor (5 used) shielded twisted pair
instrument cable.
• Conductor size dependent on cable length.
• BELDEN 3120A, DEKORON or equivalent.
• Max: BELDEN 3120A = 500m (1640 ft).
3 pairs, 1 conductor not used.
Remote Sender
Status LED
• Green when powered
• Blinks while working
correctly
• Solid while not transmitting
TEST Button
• Press and hold to test level
relay action
Remote Receiver
Status LED
• Green when powered
• High illumination =
strong signal
• Low illumination = weak signal
Signal Contact
• Signal can be read with
voltmeter across Signal
contact point and earth screw
(or other ground reference)
• 2.4-2.5V is full signal.
0V is no signal
Use long nose
pliers to extract
terminals
**
**
microwave sender
STATUS
remote
Signal
STATUS
Gladiator Remote Amplifier
+
A
1L
+
N
B
RED
BLACK
BLUE
WHITE
BROWN
Is
SENSOR DC-In AC-In*4-20mA
COMMS
MIC-SENDER
RED
BLACK
BROWN
SLAVE IN
MASTER OUT
TEST IN
RELAY 1
NC
COM
NO
RELAY 2
NC
COM
NO
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Remote Receiver
Sender
Inputs model dependent
Add wire between
terminal 8 and
ground screw
Add wire between
terminal 8 and
ground screw
1 2 3 4 5 6 7 8 9 10
BRN
RED
BLK
1 2 3 4 5 6 7 8 9 10
BRN
RED
BLK
WHT
BLU
Ground screw Ground screw
*AC-In is replaced by 36-60VDC with Power Input
Option ‘C’.
**Ground the housing to vessel if vessel is metallic.
Ground the housing to plant ground if vessel is
non-metallic.

Table of Contents