EasyManua.ls Logo

Helmholz NETLink PRO Series - Setting up the OPC Toolbox Demo Client

Helmholz NETLink PRO Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NETLink
®
PRO family Application Examples
11
The CPU can be determined with “Test” (this feature is op-
tional and must not be executed in mandatory).
The connection test was successful and can be confirmed
with “OK”.
The OPC server is now fully configured for a NETLink
®
to PLC
connection.
If you want to set up multiple connections within a device, the
PLC no.” has to be unique for each connection. These num-
bers must be different.
3.2
Setting up the OPC Toolbox demo client
The following steps are provided as an example only and are
not obligatory for customer applications. They serve as a visual
check whether data exchange is taking place.
Start program module “OPC Toolbox demo client” with
Start/Programs/Systeme Helmholz/S7-OPC-Server. The various tab
cards are displayed below.
The “OPC Servers" field opens first:
Choose the CPU address
as
PLC-number to pre-
vent duplicates

Related product manuals