10  Zone  LED  Alarm  Panel  -  Engineering  Manual   
 
22
6.2.4 - How to set zone function 
In Zone Function, Security type zones can be assigned different functions. These are   
1= Immediate Zone, 2 = Timed Zone, 3 = Inhibited Zone.      
Immediate Zone:
   
Use this function when the zone is not part of an entry/exit route. When the system is SET, 
activation of an immediate zone will cause a full alarm condition. 
Timed Zone: 
 
A timed zone would be used to protect an entry/exit route. Opening the door or triggering 
the sensor in this type of zone when the system is SET will start the entry timer. 
Inhibited Zone:   
A time-inhibited zone operates as an immediate zone unless a timed zone has been operated 
and a timer started. Such a zone should be utilized to allow passage between the entry/exit 
door and the control panel or key pad when there are detectors present. 
 
 
 
Set zone Immediate function 
 
Under Engineer Menu/Setup Program, the program 
Full mode is chosen. LED 1 and LED 2 is flashing.   
 
 
·
Press          to program Immediate Zone. 
LED 3~10 ON indicate selected immediate   
zones. 
Default settings are on. 
 
·
To edit the other zones press Zone number   
(1~10). If selected, LED is on. 
    If you select Zone 2 to be immediate zone, 
 
·
Press            to accept the change 
Or press            to cancel.