10  Zone  LED  Alarm  Panel  -  Engineering  Manual   
 
27
6.4 - Setup Zones Attributes       
There are three attributes for Zone: 1 = Omit Allowed, 2 = Double Knock, 3 = Chime. You can 
set it ON or OFF. 
Omit Allowed: 
When a Zone is programmed as Omit Allowed, the panel allows the Zone to be Omitted for 
one set period by the user when setting the system.   
Note: The zone must to be set to security then it can be set omit allowed. 
Double Knock: 
Double knock programming is used when zones are likely to create false activations. 
Double knock requires two activations within 10 minutes of the same Zone or a Zone left 
open for 10 seconds. 
Chime: 
If a Security Zone is programmed as Chime, you can hear special tone when it is triggered 
in DAY mode. 
Note: The zone must to be set to security then it can be set Chime. 
 
To operate the Setup Zone attributes as follow. 
e.g. Set zone 2 to have Omit Allowed, Double Knock and Chime attributes (set ON). 
 
Omit Allowed 
·
Under Engineer mode 
·
Press        to select Zone Attributes menu. 
 
 
·
Press zone No. to select zone (0~9). 
If you set Zone 1 attribute is omit allowed. 
 
 
·
Press        to select Omit Allowed.       
 
 
·
Press          to accept the change 
Or press          to cancel.     
 
 
Double Knock 
·
Under Engineer mode. 
·
Press        to select Zone Attributes menu. 
·
Press zone No. to select zone (0~9) 
If you set Zone 4 attribute is double knock. 
 
·
Press        to select double knock.