10  Zone  LED  Alarm  Panel  -  Engineering  Manual   
 
26
6.3 - Setup Zones Type   
6.3.1 - How to set Zone Type     
There are six types for Zone: 1 = Security, 2 = PA, 3 = Fire, 4 = Tamper/24Hr, 5 = Door Bell,   
0 = Not Used.   
Security: 
The  system  comes  supplied  with  service  links  fitted  to  the  zone  terminals  to  simulate  a 
closed circuit. As each zone is connected these links should be removed. All zones are fully 
programmable. This is 12hr operates when panel is set.   
PA: 
A  Zone  may  be  programmed  for  audible  PA  and  should  be  wire  in  series.  This  is  24hr 
operates if panel is set or unset. 
Door Bell: 
This  feature  can  be  programmed  into  any  Zone.  A  doorbell  will  not  operate  whilst  the 
entry/exit  timers  have  started,  when  the  system  is  in  full  alarm  condition  or  whilst  in 
programming mode. 
Fire: 
If you choose to utilize a zone as a fire zone then no other detectors may be wired into this 
zone. Therefore a zone cannot be both fire and intruder. This is 24hr operates when panel is 
set or unset. 
Tamper/24Hr: Provides 24 hour monitoring when set or unset. 
Not used 
A zone may be programmed as Not used, and then is ignored by the panel. 
 
To operate the Setup Zone type as follow. 
e.g. Change zone 5 type to Tamper/24Hr. 
·
Under Engineer mode. 
 
·
Press          to select set up Zone Type.   
 
·
Press a number button to select Zone to be             
configured. 
Then press          to select zone 5, Zone type   
of Zone 5 is Security.   
 
·
Press          to select Tamper/24Hr 
 
 
·
Press          to accept the change. Or press   
    to cancel. Press          to return to Engineer mode.