rev00 Installation, use and maintenance manual
DDS-DCS Dehumidifier for small swimming pools
24 - 48
4 TECHNICAL DATA
4.1 TECHNICAL DATA TABLES
Model
040
050
060
070
090
100
Dehumidifying capacity 30° - 80% R.H.
L/day
46
52
62
68
89
98
Dehumidifying capacity 30° - 60% R.H.
L/day
37
41
48
54
71
76
Dehumidifying capacity 27° - 60% R.H.
L/day
33
36
43
46
62
67
Dehumidifying capacity 20° - 60% R.H.
L/day
24
26
30
33
45
50
Nominal air flow
m3/h
350
450
500
600
700
800
Available static pressure
Pa
40
40
40
40
40
40
Sound level (1)
db(A)
43
45
46
47
48
49
Hot water coil capacity (2)
kW
3.7
4.5
4.8
6.1
6.8
7.5
Load losses hot water coil without valve
kPa
8
11
12
25
30
36
Load losses hot water coil with valve
kPa
11
16
17
35
42
50
Electrical heaters capacity
Kw
1.5
1.5
1.5
2
3.6
3.6
Power supply
V/ph/Hz
230 / 1 / 50
Nominal power consumption
kW
0.84
0.86
1
1
1.5
1.5
Maximum power consumption
kW
1.1
1.1
1.2
1.2
1.9
1.9
Nominal absorbed current
Amp
3.9
3.9
4.5
4.5
7.3
7.4
Maximum absorbed current
Amp
5.1
5.1
5.6
5.7
9
9
Inrush current
Amp
19
19
19
19.1
37.4
37.4
Nominal power with electrical heaters
kW
2.34
2.36
2.5
3
5.1
5.1
Maximum power with electrical heaters
kW
2.6
2.6
2.7
3.2
5.5
5.5
Nominal current with electrical heaters
Amp
10.4
10.4
11
13.2
23
23
Maximum current with electrical heaters
Amp
11.6
11.6
12.1
14.4
24.6
24.6
Inrush current with electrical heaters
Amp
25.5
25.5
25.5
27.8
53.1
53.1
Working temperature range
°C
12 36
Working humidity range
%
45 95
Refrigerant gas
R410A
(1) Sound level declared at 1 m in free field
(2) Heat output with water 80 / 70°C , ambient 30°C