7.4 FIRST STARTING
First starting, calibration and configuration of the unit should be done only by qualified staff.
DO NOT IMPROVISE, UNIT DISFUNCTION DANGER!
Before proceeding with the start of the unit, check that all the closing panels are placed correctly and closed properly.
For the first start follow carefully these directions:
Check that all the connections (hydraulic, electric and aeraulic) are properly installed and that all
the directions indicated on labels, user manual and electric drawing are followed.
Check that the refrigerant circuit taps, if present, are open and that the hydraulic plant is cracked, by eliminating any residual air,
charging it gradually and opening the cracking devices on the top side.
Check that there is not any water loss.
The unit is delivered ready to function: supply the unit, if it is in OFF, press the ON/OFF button to turn it on.
For the basic setting (i.e. the humidity set point) make reference to the previous paragraph titled “advanced control”.
For the advanced setting (optional) make reference to the following paragraph.