rev 10 USER MANUAL
RS Dehumidifiers for radiant systems
14 - 52
1. TEMPERATURE / PARAMETERS values
2. COLD CALLING icon
Led OFF = Cold calling OFF
Led ON = Cold calling ON
Led flashing = Cold calling ON, but waiting for the re-starting time
3. HOT CALLING Icon (if active)
Led OFF = Hot calling OFF
Led ON = Hot calling ON
4. DEFROST CALLING icon
Led OFF = Defrost calling OFF
Led ON = Defrost calling ON
5. FANS CALLING icon
Led OFF = Fans calling OFF
Led ON = Fans calling ON
6. DIGITAL INPUT ACTIVATED BY HUMIDISTAT (if active)
Led On = Active digital input
Led flashing = Compressor off because of missed humidistat consent
7. ALARM icon
Led OFF = No alarms present
Led flashing = Alarm present
5.2 USER PARAMETERS
To enter the user parameters setting menu, it is necessary to:
1. Hold down for 3 seconds the keys UP () and DOWN () till you see on the display the first variable. A sound will be
emitted.
2. Select with the keys UP () or DOWN () the variable to modify.
3. It is possible to change the value holding the SET key and the key UP () or DOWN ().
4. At the end of the setting, to exit the menu, hold down the keys UP () or DOWN () or wait 30 seconds without.
The status of the unit (OFF or ON) appears on the display. A sound will be emitted.
5. Confirmation of the modifications will be automatic after the exit from the configuration menu.
PARAM
DESCRIPTION
DEFAULT

Setting temperature set-point (if active)
26,0

Display temperature:
- water probe
Reading

Display temperature:
- coil probe - (version A isothermal)
- ambient probe - (version I hybrid)
Reading

Software release
Reading
For the dehumidifiers with cold integration, the defrost is cyclic, every 120 minutes.
This time is set by default.