X-AI 32 02  3 Product Description 
HI 801 055 E Rev. 4.00  Page 15 of 60 
3.4.4  System Bus Indicators 
The system bus LEDs are labeled Sys Bus. 
LED  Color  Status  Description 
On 
Physical and logical connection to the system bus 
module in slot 1. 
Green 
Blinking1 
No physical connection to the system bus module in 
slot 1. 
A 
Yellow Blinking1 
The physical connection to the system bus module 
in slot 1 has been established. 
No connection to a (redundant) processor module 
running in system operation. 
On 
Physical and logical connection to the system bus 
module in slot 2. 
Green 
Blinking1 
No physical connection to the system bus module in 
slot 2. 
B 
Yellow Blinking1 
The physical connection to the system bus module 
in slot 2 has been established. 
No connection to a (redundant) processor module 
running in system operation. 
A+B Off  Off 
Neither physical nor logical connection to the 
system bus modules in slot 1 and slot 2. 
Table 5:  System Bus Indicators 
 
3.4.5 I/O Indicators 
LED  Color  Status  Description 
On 
The input current is > 4 mA or greater than the HIGH 
switching point (dig) configured in SILworX.  
Blinking2 
Channel fault (module field or hardware fault). Input 
current > 20 mA 
Channel 
1...32 
Yellow 
Off 
The input current is < 4 mA or less than the LOW 
switching point (dig) configured in SILworX. 
Blinking2 
Field fault on at least one channel or supply (open-circuit, 
short-circuit, over-current, etc.)  
Depending on the configured current thresholds. 
Field  Red 
Off  No faults on the field zone. 
Table 6:  I/O Indicators