X-AI 32 02  3 Product Description 
HI 801 055 E Rev. 4.00  Page 27 of 60 
3.7 System Cable 
The system cables are used to wire the connector boards with the field termination 
assemblies. 
 
 Identical Cable Plugs 
Figure 9:  System Cable 
Depending on the type of connector board, two different types of system cables are 
available. 
 
3.7.1  System Cable X-CA 005 
The X-CA 005 system cable is used to connect the X-CB 008 03/04/07 and 
X-CB 019 03/04 connector boards to the field zone via field termination assemblies or inline 
terminals. 
General 
Cable  LIYCY-TP 38 x 2 x 0.25 mm² 
Wire  Finely stranded  
Average outer diameter (d)  approx. 16.8 mm 
Minimum bending radius 
Fixed laying 
Flexible application 
 
5 x d 
10 x d 
Combustion behavior 
Flame resistant and self-extinguishing in 
accordance with IEC 60332-1-2, -2-2 
Length 8…30 m 
Color coding  Based on DIN 47100, see Table 15. 
Table 17:  Cable Data X-CA 005