X-AI 32 02 4 Start-up
HI 801 055 E Rev. 4.00 Page 39 of 60
Name Data type R/W Description
SP HIGH DINT W Lower limit of high level
SP HIGH (switching point HIGH) is the limit value: if this limit
is exceeded, the module detects a HIGH and switches the
Channel LED on.
Restriction: SP LOW ≤ SP HIGH
Default setting: 40 500 (4.05 mA)
-> Ch. value
[BOOL]
BOOL R
Boolean channel value in accordance with the switching
values limits LOW and HIGH.
Ton [µs] UDINT W Time on delay
The module only indicates a level change from LOW to HIGH
if the HIGH level is present for longer than the configured time
t
on
.
Important: The maximum reaction time T
R
(worst case) for this
channel is extended by the delay time, since a signal change
is not detected until the delay time has expired.
Range of values: 0 … (2
32
- 1)
Default setting: 0
Toff [µs] UDINT W Time off delay
The module only indicates a level change from HIGH to LOW
if the LOW level is present for longer than the configured time
t
off
.
Important: The maximum reaction time T
R
(worst case) for this
channel is extended by the delay time, since a signal change
is not detected until the delay time has expired.
Range of values: 0 … (2
32
- 1)
Default setting: 0
-> State LL BOOL R TRUE: Value associated with the LL event state
FALSE: Value out of the range associated with the LL event
state
-> State L BOOL R TRUE: Value associated with the L event state
FALSE: Value out of the range associated with the L event
state
-> State N BOOL R TRUE: Value associated with the N (normal) event state
FALSE: Value out of the range associated with the N (normal)
event state
-> State H BOOL R TRUE: Value associated with the H event state
FALSE: Value out of the range associated with the H event
state
-> State HH BOOL R TRUE: Value associated with the HH event state
FALSE: Value out of the range associated with the HH event
state
redund. BOOL W Requirement: The redundant module must be configured.
Acivated: Activate the channel redundancy for this channel
Deactivated: Deactivate the channel redundancy for this
channel
Default setting: Deactivated
Redundancy value BYTE W Setting for determining the redundancy value.
Min
Max
Average
Default setting: Max
It is only displayed in the redundancy group tab!
Table 24: Tab: I/O Submodule CI32_02:Channels in the Hardware Editor