(APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 95
ELECTRICAL CHARACTERISTICS
Symbol Parameter Conditions Minimum Typical Maximum Unit
Power supply (terminals 8÷36V, –BAT, +BAT)
8÷36V Module supply voltage 8 36 VDC
+BAT
Power supply of the
outputs
8 36 VDC
I
BAT
Supply current
8÷36 V=12
V
200 mA
I
BAT
Supply current
8÷36 V=24
V
100 mA
P
BAT
Power consumption 2.5 W
PNP digital input (MAN, AUTO terminal)
V
IN
Input voltage -0.7 36 V
V
IL
Low level input voltage 1 V
V
IH
High level input voltage 5 V
I
IL
Low level input current V
IN
= 0V 0 100 uA
I
IH
High level input current V
IN
= 12V 0.8 1 mA
CAN Bus (terminals CANS, CANL, CANH)
V
IN
Input voltage -58 +58 V
DR
CAN
Baud rate 50 Kbps
J1939 BUS (terminals J1939S, J1939L, J1939H)
V
IN
Input voltage -27 +40 V
DR
CAN
Baud rate 50 Kbps
NPN digital inputs (RC, BPA, ATA, NA, PEM, ENT1, ENT2, ENT3, ENT4, ENT5, SETA terminals)
V
IN
Input voltage -0.7 +36 V
V
IL
Low level input voltage 1 V
V
IH
High level input voltage 5 V
I
IL
Low level input current V
IN
= 0V 2 2.5 mA
I
IH
High level input current V
IN
= 24V 0 100 uA
High speed digital inputs (PCK1, PCK2 terminals)
V
IN
Input voltage 30 VAC
I
IN
Input current V
IN
= 12VAC 5.5 6 mA
F
IN
Input frequency V
IN
= 12VAC 3600 Hz
Analogue inputs (NC, P, T, Anc, GND, DI terminals)
V
I
Input voltage 5 V
R
NC
Fuel level resistance 0 400 Ω
R
P
Pressure resistance 0 200 Ω
The control unit must be mounted at the front of an electrical panel, if possible in
the centre to allow easy wiring.
There are no special ventilation requirements due to the low power consumed by
the control unit.
The surface areas of the equipment and the external face should be cleaned with
a damp cloth.
The equipment is included within the measurement category CAT III 600 V for
measurements performed in the building installation.
Disconnection means should be incorporated to the xed installation in accord-
ance with installation regulations. Such means must have contact separation for
all poles that provide full disconnection in category III overvoltage conditions.
The disconnecting means must be accessible by the user. The negative terminal
of the battery, the chassis of the electrical panel and the chassis of the genera-
tor set must all be earthed.
The manufacturer is not liable for any damage caused by not following the war-
nings and / or recommendations indicated in the manual, since the protection
ensured by the equipment may be compromised.
Maximum height assigned above sea level is 2000m
THIS EQUIPMENT MAY GENERATE RISK OF DAMAGE IF HANDLED IMPROPERLY.
IT MUST BE INSTALLED BY QUALIFIED PERSONNEL.
IT IS NECESSARY TO CONSULT THE DOCUMENTATION FOR EQUIPMENT.
ATTENTION: RISK OF DAMAGE.