44
Simplied Measurement for Earth Resistance
(Simplied Measurement Method, Two-pole Method)
2.7 Simplied Measurement for Earth
Resistance
(Simplied Measurement Method,
Two-pole Method)
DANGER
Use the neutral side (ground side) of the commercial
power supply for this measurement. Prior to
connection, use a voltage detector etc. to make sure
that it is going to be connected with the neutral side
and take caution for electric shock.
This device can be connected to the neutral side of
an outlet with a voltage-to-ground of 300 V or less,
or to the wire on the neutral side of the breaker's
secondary side with a voltage-to-ground of 150 V or
less. Do not connect with anything other than those
specied above. It can be hazardous.
WARNING
Use the optional test lead L9787 for simplied
measurement for safety. Connecting the
measurement cables L9841, L9842-11, L9842-22,
L9843-51 and L9843-52 to a commercial power
supply may cause electric shock.
This device can output a voltage of approx. 30 V.
Although the device has a dust-proof, jet-proof and
water-proof structure, the device should always
be dried before using it for measurement so as to
avoid electric shock.