EasyManua.ls Logo

Hitachi EH-150 - (2) Various Kinds Setting

Hitachi EH-150
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10 Troubleshooting
(2) Various kinds setting
Various kinds setting start
DIP SW bit 1 is ON
and Bit 2, 3 is OFF
Some parameters can be changed
only with the dip switch
configuration shown as left.
N
Y
DIP SW bit 4 to 8 are
all OFF
This DIP SW configuration is not
allowed to use.
The bit 4 to 8 is for the lowest
octet of IP address.
Y
N
Online “EH-ETH2 Configurator”
Check if communication setting
of “EH-ETH2 Configurator” is
correct.
N
Y
Complete of various kinds setting
Set up an appropriate value
according to the error message.
Y
N
Abnormal setting
There is response of
ping command
N
Y
The network is not on line
physically or logically. Check the
below items.
- Communication cable and HUB
etc.
- Wrong IP address in the host
computer.
- Duplication of IP address to
other stations.
- MAC address is not solved.
*1
*1: Refer to "
CAUTION at the time of the module exchange
" of "9.2 Regular Check".
10-3

Table of Contents