Chapter 2 Specifications
2 – 70
Specifications
Item Specification
Number of control axes 1 axis
Highest frequency 400 k pulse/s
Capacity 256 points Positioning data
Setting procedure 1. Sequence program
2. Positioner (Note, a positioner is optional.)
Method 1. Absolute system
2. Absolute system + Increment system
3. Increment system
Positioning instruction 1. Pulse specifying
2. μm specifying
3. inch specifying
4. degree specifying
Speed instruction Automatic, manual, and homing
6.25 pulse/s to 400 k pulse/s
μm/s, inch/s, degree/s input function
Speed stage 10 stages
Acceleration and
deceleration system
Trapezoid acceleration and deceleration
S-curve acceleration and deceleration (3-stage acceleration and deceleration)
Acceleration and
deceleration time
1 to 65,535 ms
Backlash 0 to 255 pulse
High and low limit setting +2,147,483,647 to -2,147,483,648 pulse
Pulse output method 1. Pulse chain (CW/CCW)
2. Clock + direction signal (CK/Direction)
(DIP switch No.1 and No.2 set the choice of pulse output system and the
switching of each positive and negative logic.)
Positioning
Pulse output procedure 1. Open collector output (Photo-coupler insulation)
2. Line driver output (Photo-coupler insulation)
Homing function 1. Free home position
2. Low speed homing
3. High speed homing 1
4. High speed homing 2
5. Absolute value encoder homing
Teaching Possible
Manual (JOG) operation Pulse output by manual input signal
Operation when CPU has stopped Operation is possible via I/O set or using the positioner
Absolute value encoder input Supports to Σ series / Σ II series by Yasukawa Electric Co. and P series by
SANYO electric Co.
Internal current consumption
300mA maximum
(continued on the following page)
Note - When the CPU is stopped during operation, the motor decelerates and stops.
- The maximum travel per one movement is 2,147,483,647 pulses. If the operation is performed exceeding