L300P Inverter
Inverter Mounting
and Installation
2–15
The following table lists wire and fuse sizes for 400V models.
Note 1: Field wiring must be made by a UL-listed and CSA certified ring lug terminal
connector sized for the wire gauge involved. The connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66 ft (20m).
Motor
Output
400V
Inverter
Models,
L300P
Wiring *1
Power Lines *3 Chassis Ground
Brake Res.
HP kW
AW G
*1, *3
mm
2
*3
Fuse
(UL-
rated,
class J,
600V)
Breaker
( GFI
type) *2
AW G ,
rec.
AW G ,
UL
mm
2
AW G
mm
2
2 1.5 –015HFU2, HFE2 20 2 10A 10A 16 14 1.25 18 2
3 2.2 –022HFU2, HFE2 18 2 10A 10A 16 14 1.25 16 2
5 4.0 –040HFU2, HFE2 16 2 15A 15A 16 14 1.25 14 2
7.5 5.5 –055HFU2, HFE2 14 2 15A 30A 14 14 2 12 2
10 7.5 –075HFU2, HFE2 12 3.5 20A 30A 10 12 3.5 10 3.5
15 11 –110HFU2, HFE2 8 5.5 30A 50A 8 10 5.5 8 5.5
20 15 –150HFU2, HFE2 6 8 35A 60A 8 10 8 8 5.5
25 18.5 –185HFU2, HFE2 6 14 50A 60A 4 10 14
30 22 –220HFU2, HFE2 4 14 50A 75A 4 10 14
40 30 –300HFU2, HFE2 3 22 70A 100A 3 10 22
50 37 –370HFU2, HFE2 1 14 || 14 80A 100A 3 8 22
60 45 –450HFU2, HFE2 1 38 100A 150A 1 8 22
75 55 –550HFU2, HFE2 1/0 22 || 22 125A 175A 1 6 30
100 75 –750HFU2, HFE2 1/0 || 1/0 30 || 30 150A 225A 1/0 6 50
125 90 –900HFU2, HFE2 3/0
(1/0 || 1/0)
30 || 30 200A 225A 3/0 6 50
150 110 –1100HFU2, HFE2 2/0 || 2/0 50 || 50 250A 350A 3/0 4 80
175 132 –1320HFU2, HFE2 2/0 || 2/0 60 || 60 300A 350A 4/0 4 100