24
Intelligent Output Terminal Listing
Analog Input Configuration
The following table shows the parameter settings and [AT] state required
to select various analog input sources.
Analog Output Function Listing
The following table shows the functions available for assignment to the
analog output terminal via terminal [AM], option set by C028:
Symbol Code Input Terminal Name
RUN 00 Run signal
FA1 01 Freq. arrival type 1 – constant speed
FA2 02 Freq. arrival type 2 – over-frequency
OL 03 Overload advance notice signal
OD 04 Output deviation for PID control
AL 05 Alarm signal
Dc 06 Analog input disconnect detect
FBV 07 PID second stage output
NDc 08 Network detection signal
LOG 09 Logic output function
A005 [AT] External Frequency Command Input
00 OFF [O]
ON [OI]
01 (ignored) Sum (O + OI)
02 OFF [O]
ON Keypad potentiometer
03 OFF [OI]
ON Keypad potentiometer
Option
Code
Function Name Description
Corresponding
Signal Range
00 Analog freq. monitor Actual motor speed 0 to max. freq. (Hz)
01 Analog current
output monitor
Motor current (% of max.
rated output current)