18
“B” Group: Fine-tuning Functions
A145 ADD frequency 0.0
A146 ADD direction select
• 00 Plus (adds A145 value to output frequency)
• 01 Minus (subtracts A145 value from output
frequency)
00
Func.
Code
Name / Description
Default
Value
–FEF / –FU
Set
Value
B001 Selection of automatic restart mode
• 00 Alarm output after trip, automatic restart
disabled
• 01 Restart at 0Hz
• 02 Resume operation after frequency
matching
• 03 Resume previous freq. after freq. matching,
then decelerate to stop and display trip info
00
B002 Allowable under-voltage power failure time 1.0
B003 Retry wait time before motor restart 1.0
B004 Instantaneous power failure / under-voltage trip
alarm enable
• 00 Disable
• 01 Enable
00
B005 Number of restarts on power failure / under-
voltage trip event
• 00 Restart 16 times
• 01 Always restart
00
B012/
B212
Level of electronic thermal setting Rated
current of
each inverter
B013/
B213
Electronic thermal characteristic
• 00 Reduced torque • 01 Const. torque
01
B021 Overload restriction operation mode
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
01
B022 Overload restriction setting Rated
current
x 1.5
Func.
Code
Name / Description
Default
Value
–FEF / –FU
Set
Value